[. . . ] XL 800 Series
FOR SMOKE CONTROL
HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION AND COMMISSIONING INSTRUCTIONS CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Before Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] No further wiring is necessary.
ROOM 1
71 72 LonWorks 73 I/O MODULE 74
XCL8010AU 12
LonWorks 76 I/O MODULE 77
75 78
Multiple Rails in Single Cabinet
The multiple rails of a controller system are connected in series.
Connect the rail ends as follows:
Power supply via power supply terminals 73, 74 or 77, 78 Communication via communication terminals 71, 72 or 75, 76
71 72 73 I/O MODULE 74 71 72 73 I/O MODULE 74 71 72 73 I/O MODULE 74 71 72 73 I/O MODULE 74 75
ROOM 2
73 I/O MODULE 74
LonWorks LonWorks I/O MODULE LonWorks 76 I/O MODULE 77
75 78
I/O MODULE I/O MODULE 76 77
78 75
Fig. Wiring the LONWORKS Bus I/O modules in separate rooms
XCL8010AU 12
I/O MODULE 76 77
78
Maximum Cable Length Max. cable length: 1200 meters (4000 ft), supervised.
How to Connect Panel Bus and LONWORKS Bus Mixed Controller Systems
Connecting I/O Modules
For connecting the I/O modules with each other, proceed as described for single-bus controller systems.
Connecting I/O Modules to the XCL8010AU
Fig. Wiring the power supply and the communication lines to the I/O modules Panel Bus I/O Modules
Connect communication terminals 71 74 or 75 78 of
LonWorks Bus I/O Modules in Separate Rooms
In this scenario, only communication lines must be connected between the rooms.
Connect the last module of room 1 to the first module of
Panel Bus I/O modules to communication terminals 71 74 or 75 78 of the XCL8010AU Controller Module using either Bridge connectors for flush mounting on a single DIN rail or Cables for separate mounting, e. g. , on multiple rails, separate cabinets, etc. LONWORKS Bus I/O Modules
Connect communication terminals 71 74 or 75 78 of
room 2: via communication terminals 71, 72 or 75, 76
LONWORKS Bus I/O modules to LONWORKS terminals 11 14 of the XCL8010AU using cables.
EN1B-0410GE51 R0908A
12
Excel 800
Description of the XCL8010AU Controller Module
Panel Bus modules
71 72 73 74 75 76 77 78 71 72 73 74
Panel Bus modules
XCL8010AU 76 77
78 75 71 72 73 74 75 76 77 78
11 12 13 14
1 2 3 4
LonWorks Bus modules
71 72 73 74 75 76 77 78
Fig. Mixed bus system correct wiring
Panel Bus modules
71 72 73 74 75 76 77 78 71 72 73 74
LonWorks Bus modules
XCL8010AU 76 77
78 75 71 72 73 74 75 76 77 78
11 12 13 14
1 2 3 4
Fig. Mixed bus system incorrect wiring
Setting Address of Panel Bus I/O Modules
Each Panel Bus I/O module is assigned its own unique address. For the sake of clarity for maintenance personnel, it is recommended that you address the Panel Bus I/O modules in ascending order 0 through F. HEX switch settings and addresses HEX switch address HEX switch address 0 01 8 09 1 02 9 10 2 03 A 11 3 04 B 12 4 05 C 13 5 06 D 14 6 07 E 15 7 08 F 16
Use the rotary HEX switch to set the address to the one
already defined during engineering.
13
EN1B-0410GE51 R0908A
Mounting/Dismounting Modules
Excel 800
LONWORKS Bus Topologies
4 4
LOCK
The LONWORKS Bus is a 78-kilobit serial link that uses transformer isolation so that the bus wiring does not have a polarity. it is not important which of the two LONWORKS Bus terminals are connected to each wire of the twisted pair. The LONWORKS Bus does not need to be shielded on the controller module side. The LONWORKS Bus can be wired in daisy chain, star, loop or any combination thereof as long as the maximum wire length requirements are met. HEX switch location
NOTE:
If the HEX switch setting is changed, the Panel Bus I/O module will revert to its default configuration. With LONWORKS Bus I/O modules, the HEX switch is without function.
The recommended configuration is a daisy chain with two bus terminations. LONWORKS Bus lengths, and its simple structure presents the least number of possible problems, particularly when adding on to an existing bus.
C-Bus Topologies
Via the C-Bus up to 30 C-Bus devices (e. g. , controllers, etc. ) can communicate with one another and a PC central. The CBus must be connected via the individual controllers (open ring). NOTE: Star connection is not allowed because uncontrollable line reflections may occur.
Setting the I/O Bus Switch
Set the I/O Bus switch S2 of the XCL8010AU Controller
Module depending on the modules connected to terminals 71 78 and the desired communication as follows: Table 10. I/O Bus switch settings communication LONWORKS Bus only S2 setting LON terminals 71 74 LONWORKS Bus 75 78 LONWORKS Bus 11 14 LONWORKS Bus Panel Bus and LONWORKS Bus Panel 71 74 Panel Bus 75 78 Panel Bus 11 14 LONWORKS Bus
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install the
Excel 800 System. More than one disconnect switch may be required to deenergize the system.
Do not reconnect the power supply until you have
completed the installation.
NOTE:
The terminal socket of each I/O module can be mounted and wired before inserting and locking the corresponding electronic module.
Fig. S2 I/O Bus switch
EN1B-0410GE51 R0908A
14
Excel 800
Mounting/Dismounting Modules
Mounting/Dismounting Controller/Sockets
Mounting Sockets
NOTE: When using both Panel Bus and LONWORKS Bus I/O modules in an Excel 800 System, group both Panel Bus modules (light-gray) and LONWORKS Bus I/O modules (dark-gray), e. g. , on different rails. Up to 10 Panel Bus I/O modules can be mounted to one side of the XCL8010AU. [. . . ] Manual overrides (toggle switches) The XFR824AU and XFLR824AU Relay Output Modules are equipped with six manual overrides: one for each relay output. These toggle switches can manually be set to either "auto" or "0" or "1". Relay Output Module status LED behavior mode automatic mode, state "logical ON" automatic mode, state "logical OFF" override mode (setting "0") override mode (setting "1") LED ON OFF flashes flashes N. O. * N. C. * (direct) (reverse) ON OFF OFF ON OFF ON ON OFF
*As configured during engineering.
29
EN1B-0410GE51 R0908A
Description of the I/O Modules
Excel 800
Connection Examples
71 COM A 72 73 74
COM B 24 V~ 24 V~0
COM A COM B 24 V~ 24 V~0
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
NO NC COM CON
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64
25
12
14507287 SERIES POWER MODULE
Fig. XF824AU connection example
M
71 COM A 72 73 74
COM B 24 V~ 24 V~0
COM A COM B 24 V~ 24 V~0
75 76 77 78
72 COM B 73 74
24 V~ 24 V~0
71 COM A
NO NC COM CON
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64
25
3
2 M
1
14507287 SERIES POWER MODULE
Fig. [. . . ]